Installing and Maintaining BN Platforms
3-6 109352-E Rev. A
Electrical Requirements
The installation site must provide a power source that meets the following
electrical requirement: 200 to 240 VAC at a maximum of 13 A @ 230 VAC.
The power required for the BCN RLC is 100 VAC to 240 VAC at a maximum of
8a @ 230 VAC and 16a @ 100 VAC.
Locate the BCN within 8 ft (2.5 m) of the wall receptacle. Table 3-3 lists the types
of wall receptacles the BCN uses.
Table 3-3. Wall Receptacle Requirements
Country Receptacle Voltage
Branch
Current
United
States or
Canada
National Electrical Manufacturers
Association (NEMA) L6-20R standard
receptacle
208 to 220
volts
20 A
European
countries
IEC 309 standard receptacle 240 volts 16 A
Other
countries
Your BCN distributor supplies the proper
cord. It is shipped with the unit from the
factory.
200 to 240
volts
20 A